According to article 300.5 of the 2005 NEC Code, low voltage landscape lighting wire needs to be buried to the following depths:

Location of Wire
Minimum Burial Depth*
All locations not specified below
6 inches
In trench below minimum 2" thick concrete
6 inches
Under a building
In raceway only
Under roads, alleys, public driveways and parking lots
24 inches
Under one- and two-family dwelling driveways and outdoor parking areas and used only for dwelling-related purposes
18 inches
In or under airport runways, including adjacent areas where trespassing is prohibited
18 inches
*Note – depth is measured from the top surface of wire to top surface of finished grade or surface material. Where solid rock prevents compliance with these depths, a direct burial raceway can be used, encased in concrete at least 2" thick on top and extending down to the rock.